Close

Safetec BG02.600 BG02.610 Power Supply Module System SDS-48

$1,200.00
In stock
SKU
E193
BG02.600 Power Supply Module 220/230V System SDS-48 The power supply unit is mounted inside the smoke detection panel. It contains all power connections for main and emergency supply and for the fan unit as well as fuses and terminals for relay contacts. Dimensions: 187 x 167 x 55 mm Weight: 1,2kg BG02.610 Power Supply Module 110V/ 115V System SDS-48 The power supply unit is mounted inside the smoke detection panel. It contains all power connections for main and emergency supply and for the fan unit as well as fuses and terminals for relay contacts. Dimensions: 187 x 167 x 55 mm Weight: 1,2kg Only for 110V/ 115V supply! for TYCO SEAPLUS, NK, Wilhelmsen Unitor, minimax, etc. Maker:SAFETEC Weight: 120g NATURE (TYPE) OF DEFECT : SMOKE DETECTOR OUT OF ORDER ACTION TAKEN TO RECTIFY : CLEANED. (USED VACUUM CLEANER, COMPRESSED AIR.) DEFECT IS PERMANENTLY. CAUSE OF DEFECT Rubber diaphragm is damaged

BG02.600 Power Supply Module 220/230V System SDS-48

The power supply unit is mounted inside the smoke detection panel. It contains all power connections for main and emergency supply and for the fan unit as well as fuses and terminals for relay contacts.

Dimensions: 187 x 167 x 55 mm Weight: 1,2kg

BG02.610 Power Supply Module 110V/ 115V System SDS-48

The power supply unit is mounted inside the smoke detection panel. It contains all power connections for main and emergency supply and for the fan unit as well as fuses and terminals for relay contacts.

Dimensions: 187 x 167 x 55 mm Weight: 1,2kg Only for 110V/ 115V supply!

 

Smoke Detection System SDS-48

 SDS-2/6

How to Eliminate Air Flow Faults

 

Statistically the most frequent fault during operation of the Smoke Detection System SDS is the airflow fault. There are different reasons which may cause an airflow fault:

  • blocked smoke sampling pipe (including pre-filters if applied)
  •  damaged airflow indicator (pressure switch)
  • fault in the wiring of the airflow indicator
  •  fault in the electronic modules

If the reason for an indicated airflow is unknown, please work off the following check list:

  1. Fan Unit and 3-Way-Valves
    Ensure that the fan is running and the 3-way-valves are in position “smoke sampling”.

  2. Pipes and Hoses
    Disconnect the flexible hose at the smoke detection panel resp. extension unit. If the airflow fault disappears now, the sampling pipe is blocked by dirt or water (condensate) and must be cleaned. Drain armatures and pre-filters (if applied) to be checked for proper function.

  3. Airflow Indicator (Pressure Switch)
    If the airflow fault is still present, please short circuit the wires of the cable connected to the airflow indicator. The short circuit simulates an airflow indicator, which has detected sufficient airflow.
    If the fault indication on the display disappears now:
     - Check the wiring of the airflow indicator.
     - If the wiring is correct, the airflow indicator is defective and must be exchanged. (Remark: Most of the airflow faults are caused by damaged membranes from influence of compressed air, during pipe cleaning works).

  4. Detector Connection Module
    Measure, whether voltage is present at the output terminals of the detector connection module, where the airflow indicator is connected to. For this purpose, disconnect the cable to the airflow indicator at the detector connection module. The voltage meter should show some tenth of volt. An exact value cannot be indicated due to the fact, that the voltage exists only of short pulses. If no voltage appears (and the adjacent smoke detector is inserted), measure the voltage at input terminals 1/2 resp. 3/4 of the detector connection module. Here approx. 16 - 21V should be present. This voltage is superseded by voltage pulses and therefore the voltage display will not be very stable. If voltage at the input terminals is present, not however at the output terminals to the airflow indicators, the detector connection module is defective and must be exchanged. Please provide serial no. of the old detector connection module.

  5. Galvanic Isolator and Control Module
    Measure the voltage at the output terminals 1/2 (and 4/5 in case of 2-channel versions) of the galvanic isolators. The voltage should be at least 17V. The voltage is superseded by voltage pulses and therefore the voltage display will not be very stable.
    If the voltage is below this value, measure the voltage at the terminals 40/41 of the power supply module. The voltage is superseded by voltage pulses and therefore the voltage display will not be very stable:

    • If the voltage at the terminals 40/41 is below 20V, the control module should be exchanged. Please provide serial no. of the old control module. 

    • If the voltage at the terminals 40/41 is higher than 20V, disconnect the wires of the galvanic isolator at the terminals 1/2 resp. 4/5 and measure the voltage at the output terminals 1/2 (and 4/5 in case of 2-channel versions) again.
     

     ◦ If the voltage is still below 17V, the galvanic isolator appears to be defective and should be exchanged. Please provide serial no. of the main panel. 

      ◦ If however the voltage is correct now, the reason for the fault might be a short circuit in the detector connection module resp. smoke detectors or airflow indicator. Please provide serial no. of the old control module.

 

 

This system used to monitor the smoke for cargo hold, when the system starts, fan suction gas samples from the cargo hold, air samples through the pipeline through the dust filter, and then to detect box, to detect the smoke concentration in each independent probe test gas samples in the oven, and the analysis results feedback to the controller, when the monitored area of the smoke concentration reaches controller alarm valve value, the system will send out sound and light alarm and writing tip;System at the same time have their own the ability of fault diagnosis, when the system failure occurs, the system will be sound and light alarm and the tooltip.

 

  • All alarm sound and light hint, and detailed text information is displayed on the LCD.
  • ● Two way power input, the losing electricity all the way, the system will automatically undisturbed switching to another all the way.
  • ● Automatically monitor airflow of each sampling pipe.
  • ● Automatically monitor and control fans, two fans each other automatically switch to every 24 hours, when a fan failure, automatically swicth to another.
  • ● System can automatically detect the clean-value of each smoke detector, and compensate the corresponding alarm threshold value according to the clean-value to avoid error alarm.
  • ● All alarm information will be sent to VDR sytem in NMEA format.

 

System include the below parts can be supplied, please inquiry us:
S.N.NAMETYPEVOLTAGEIPEx. Level
1Control Panel 2×220/230VAC 50/60Hz;
or 2×110/115VAC 50/60Hz
IP56-
2Detection Box -IP56EEx ia IIC T5
 -IP56EEx ia IIC T5
3Repeater Panel 24VDCIP56-
4Relay Box 24VDCIP56-
5Fan Unit 2×220/230VAC 50/60HzIP54-
 2×110/115VAC 50/60HzIP54-

AF4-6 AF1-3

 POWER SUPPLY MODULE BG02.600

SMOKE DETECTION SYSTEM FOR CARGO HOLDS

 

1 1 PCS SDS02.112 SMOKE DETECTION PANEL,SDS-12 LINES,230/220V SDS02.112.01.tcd

 

2 1 PCS SDS02.300 REPEATER PANEL FOR WALLMOUNTING SDS-R48/G SDS02.300.01.tcd

 

3 1 PCS SDS02.440 FAN UNIT SDS-M0440 230/220V, SDS02.440.01.tcd

 

4 2 PCS BG02.032 PVC-HOSE SOCKET WITH CLAMPS, L=250MM INNER DIAM. 75MM BG02.032

 

5 12 PCS BG01.930 HOSE FITTING 3/4" MALE THREAD FOR PVC-HOSE 13/20MM BG01.930

 

6 50 M Z02.002 FLEXIBLE HOSE(PVC), INNER DIAM.13 MM GUTTASYN Z02.002

 

7 7 PCS 01-0321-20 THREE WAY BALL VALVE, 3/4" BSP 01-0321-20

 

8 7 PCS N/A SIGN PLATES FOR THREE WAY BALL VALVE N/A

 

9 46 PCS Z13.021 DRAIN VALVE Z13.021

 

10 44 PCS 01-1602-00 SMOKE ACCUMULATOR, 3/4" BSP F 01-1602-00

 

11 1 PCS BG.02.002 SPARE PART SET, STANDARD SYSTEM SDS-48 BG.02.002

 

12 1 PCS DOK02.051 MANUAL FOR SDS48, ENGLISH VERSION SDS-48 DOK02.051

 

No. 1 2 3 4 5 6 7 8 9 10a 10b 11 12 13 14a 14b 15 Bezeichnung Kabelverschraubung Anschluss Potentialausgleich Kabelkanal Stromversorgungsmodul Schlauchverschraubung Lufteintritt geöffnete Detektorbox Befestigungswinkel Rauchmelder XP95 I.S. Anschlussnippel für Absaugung Detektoranschlussmodul für max. 4 Kanäle Detektoranschlussmodul für max. 8 Kanäle Druckschalter für Luftstromüberwachung Steuermodul Relaismodul (optional) 1-Kanal-Trennwandler EEx i 2-Kanal-Trennwandler EEx i Stecker mit Leitung für E01.003 Description Cable Gland Earthbar Cable Duct Power Supply Module Adaper Nipple for Detection Line open Detector Box Mounting Strap Smoke Detector XP95 I.S. Adapter Nipple for Fan Unit Connection Detector Connection Module for max 4 Lines Detector Connection Module for max 8 Lines Pressure Switch for Airflow Monitoring Control Module Relay Module (optional) Galvanic Isolator EEx i, 1 Channel Galvanic Isolator EEx i, 2 Channels plug and cable for E01.003 Art. No. BG02.600 Z01.001 E20.002 Z03.008 BG02.810 BG02.820 E01.003 BG02.500 BG02.908 E06.101 E06.102 BG02.090

 

Pipe Connecting Parts at SDS-Devices For proper airflow it will be vital to determine the correct air pipe size. Total number of detection lines and length of air pipe must be considered by planning staff. Safetec to be informed about total number of detection lines, for evaluation of correct hose sockets. Total number of detection lines Recommended air pipe size • from farest SDS-Panel to fan unit • from fan unit outlet to end of line Art.-No. for hose socket c/w 2 hose clamps Art.-No. for PVC extension adapter below 5 m above 5 m 1 - 10 2½” (DN 65) 2½” (DN 65) BG02.032 (4 pcs.) 11 - 18 2½” (DN 65) 3” (DN 80) BG02.032 (4 pcs.) 19 - 24 3” (DN 80) 3” (DN 80) BG02.031 (4 pcs.) Z04.020 (2 pcs.)

 

Type Version (Serial Nos.) Spares (Type, safetec Art.No.) Layout SDS-M0420 From 420.0010 • Motor: Elektror, Art.No. FAN01.002-nicht mehr lieferbar • Capacitor: Type 20µF, Art.No. FAN01.003 • Alternative: Hanning, Art.No. FAN02.122 (9kg) • Capacitor: Type 12µF, Art.No. FAN02.115 • V-Belt: Art.No. FAN01.006 • Impeller: Art.No. FAN02.019 • Motor Holder: Art.No. FAN02.213 • Ball Bearing: Type: 6202-2ZC3 Art.No. FAN02.036 Type: 6205-2ZC3 Art.No. FAN01.010 Alternative: • Module including 1 motor with holder, impeller and v-belt Art. No. FAN01.001 Keilriemenantrieb 60kg Version 1: 430.0010 to 430.1530 • Motor: EMOD, Art.No. FAN02.100 *) • Capacitor: Type 16µF, 450V AC, Art.No. FAN02.111 • Impeller: Art.No. FAN02.004 – not available anymore. Alternative: Art.No. FAN02.016 • Motor Holder: Art.No. FAN02.003 **) • Ball Bearing: Type: 6202-2RS1 Art.No. FAN02.029 Version 2: 430.1540 to 430.5290 • Motor: Type EMOD, Art.No. FAN02.100 *) • Capacitor: Type 16µF, 450V AC, Art.No. FAN02.111 • Impeller: Art.No. FAN02.004 – not available anymore. Alternative: Art.No. FAN02.016 • Motor Holder: Art.No. FAN02.003 **) • Ball Bearing: Type: 6202-2RS1 Art.No. FAN02.029 SDS-M0430 230V (50kg) Version 3: From 430.5300 • Motor: Type Hanning, Art.No. FAN02.121 • Capacitor: Type 10µF, 450V AC, Art.No. FAN02.116 • Impeller: Art.No. FAN02.016 • Ball Bearing: Type 6202-2ZC3 Art.No. FAN02.036 Type 6204-2ZC3 Art.No. FAN02.037 SDS-M0431 110V 431.010 to 431.160 • Motor: Type Hanning, Art.No. FAN02.131 • Capacitor: Type 40µF, 450V AC, Art.No. FAN02.114 • Impeller: Art.No. FAN02.016 • Ball Bearing: Type 6202-2ZC3 Art.No. FAN02.036 Type: 6204-2ZC3 Art.No. FAN02.037 SDS-M0440 230V From 440.1 • Motor: Type Hanning, Art.No. FAN02.121 • Capacitor: Type 10µF, 450V AC, Art.No. FAN02.116 • Impeller: Art.No. FAN02.017 • Ball Bearing: Type 6202-2ZC3 Art.No. FAN02.036 Type 6204-2ZC3 Art.No. FAN02.037 SDS-M0441 110V From 441.1 • Motor: Type Hanning Art.No. FAN02.131 • Capacitor: Type 40µF, 450V AC, Art.No. FAN02.114 • Impeller: Art.No. FAN02.017 • Ball Bearing: Type 6202-2ZC3 Art.No. FAN02.036 Type 6204-2ZC3 Art.No. FAN02.037

 

Product Catalogue Smoke Detection System SDS-48 safetec Art.No. Description Type Remarks Outline SDS02.100 Smoke Detection Panel 0-Line SDS-0, 220/230V Smoke Detection Panel without internal detection lines. Dimensions of enclosure without fittings (H x B x D): 300 x 380 x 210 mm Weight: 12 kg Power Supply: 2 x 220/230VAC 400W SMOKE DETECTION SYSTEM SDS TEST RESET DIAGNOSES ON- / OFFLINE ON FAULT ACCEPT FIRE TOGGLE FANS safetec 1. Basic Components SDS02.104 Smoke Detection Panel 4-Line SDS-4, 220/230V Smoke Detection Panel with 1-4 internal detection lines. Dimensions of enclosure without fittings (H x B x D): 600 x 380 x 210 mm Weight: 26 kg (4 lines) Power Supply: 2 x 220/230VAC 400W Art.Nos.: SDS02.101 Detection Panel 1-Line 220/230 V 23kg SDS02.102 Detection Panel 2-Line 220/230 V 24kg SDS02.103 Detection Panel 3-Line 220/230 V 25kg SDS02.104 Detection Panel 4-Line 220/230 V 26kg SMOKE DETECTION SYSTEM SDS TEST RESET DIAGNOSES ON- / OFFLINE ON FAULT ACCEPT FIRE TOGGLE FANS safetec SDS02.108 Smoke Detection Panel 8-Line SDS-8, 220/230V Smoke Detection Panel with 5-8 internal detection lines. Dimensions of enclosure without fittings (H x B x D): 900 x 380 x 210 mm Power Supply: 2 x 220/230VAC 400W Art.Nos.: SDS02.105 Detection Panel 5-Line 220/230 V 44kg SDS02.106 Detection Panel 6-Line 220/230 V 45kg SDS02.107 Detection Panel 7-Line 220/230 V 46kg SDS02.108 Detection Panel 8-Line 220/230 V 47kg SMOKE DETECTION SYSTEM SDS TEST RESET DIAGNOS E S ON - / OFFLINE ON FAULT ACCEPT FIRE TOGGLE FANS safetec SDS02.112 Smoke Detection Panel 12-Line SDS-12,220/230V Smoke Detection Panel with 9-12 internal detection lines. Dimensions of enclosure without fittings (H x B x D): 1200 x 380 x 210 mm Power Supply: 2 x 220/230VAC 400W Art.Nos.: SDS02.109 Detection Panel 9-Line 220/230 V 57kg SDS02.110 Detection Panel 10-Line 220/230 V 58kg SDS02.111 Detection Panel 11-Line 220/230 V 59kg SDS02.112 Detection Panel 12-Line 220/230 V 60kg SMOKE DETECTION SYSTEM SDS TES T RESE T D IAGNOS ES ON- / OFFLINE ON FAULT ACCEPT FIRE T OGG LE FANS safetec Donnerstag, 1. November 2007 Page 1 Product Catalogue Smoke Detection System SDS-48 safetec Art.No. Description Type Remarks Outline SDS02.120 Smoke Detection Panel, 0-Line SDS-0,110/115V Smoke Detection Panel without internal detection lines. Dimensions of enclosure without fittings (H x B x D): 300 x 380 x 210 mm Weight: 12 kg Power Supply: 2 x 110VAC 400W SMOKE DETECTION SYSTEM SDS TEST RESET DIAGNOSES ON- / OFFLINE ON FAULT ACCEPT FIRE TOGGLE FANS safetec SDS02.124 Smoke Detection Panel 4-Line SDS-4,110/115V Smoke Detection Panel with 1-4 internal detection lines. Dimensions of enclosure without fittings (H x B x D): 600 x 380 x 210 mm Power Supply: 2 x 110VAC 400W Art.Nos.: SDS02.121 Detection Panel 1-Line 110 V 23kg SDS02.122 Detection Panel 2-Line 110 V 24kg SDS02.123 Detection Panel 3-Line 110 V 25kg SDS02.124 Detection Panel 4-Line 110 V 26kg SMOKE DETECTION SYSTEM SDS TEST RESET DIAGNOSES ON- / OFFLINE ON FAULT ACCEPT FIRE TOGGLE FANS safetec SDS02.128 Smoke Detection Panel 8-Line SDS-8,110/115V Smoke Detection Panel with 5-8 internal detection lines. Dimensions of enclosure without fittings (H x B x D): 900 x 380 x 210 mm Power Supply: 2 x 110VAC 400W Art.Nos.: SDS02.125 Detection Panel 5-Line 110 V 44kg SDS02.126 Detection Panel 6-Line 110 V 45kg SDS02.127 Detection Panel 7-Line 110 V 46kg SDS02.128 Detection Panel 8-Line 110 V 47kg SMOKE DETECTION SYSTEM SDS TEST RESET DIAGNOS E S ON - / OFFLINE ON FAULT ACCEPT FIRE TOGGLE FANS safetec SDS02.132 Smoke Detection Panel 12-Line SDS-12,110/115V Smoke Detection Panel with 9-12 internal detection lines.Dimensions of enclosure without fittings (H x B x D): 1200 x 380 x 210 mm Power Supply: 2 x 110VAC 400W Art.Nos.: SDS02.129 Detection Panel 9-Line 110 V 57kg SDS02.130 Detection Panel 10-Line 110 V 58kg SDS02.131 Detection Panel 11-Line 110 V 59kg SDS02.132 Detection Panel 12-Line 110 V 60kg SMOKE DETECTION SYSTEM SDS TES T RESE T D IAGNOS ES ON- / OFFLINE ON FAULT ACCEPT FIRE T OGG LE FANS safetec SDS02.204 Extension Panel 4-Line SDS-E4 Extends a smoke detection panel with 1-4 detection lines. Dimensions of enclosure without fittings (H x B x D): 300 x 380 x 210 mm Art.Nos.: SDS02.201 Extension Panel 1-line 13kg SDS02.202 Extension Panel 2-line 14kg SDS02.203 Extension Panel 3-line 15kg SDS02.204 Extension Panel 4-line 16kg Donnerstag, 1. November 2007 Page 2 Product Catalogue Smoke Detection System SDS-48 safetec Art.No. Description Type Remarks Outline SDS02.208 Extension Panel 8-Line SDS-E8 Extends a smoke detection panel with 5-8 detection lines. Dimensions of enclosure without fittings (H x B x D): 600 x 380 x 210 mm Art.Nos.: SDS02.205 Extension Panel 5-line 30kg SDS02.206 Extension Panel 6-line 31kg SDS02.207 Extension Panel 7-line 32kg SDS02.208 Extension Panel 8-line 33kg SDS02.212 Extension Panel 12-Line SDS-E12 Extends a smoke detection panel with 9-12 detection lines. Dimensions of enclosure without fittings (H x B x D): 900 x 380 x 210 mm Art.Nos.: SDS02.209 Extension Panel 9-line 45kg SDS02.210 Extension Panel 10-line 46kg SDS02.211 Extension Panel 11-line 47kg SDS02.212 Extension Panel 12-line 48kg SDS02.216 Extension Panel 16-Line SDS-E16 Extends a smoke detection panel with 13-16 detection lines. Dimensions of enclosure without fittings (H x B x D): 1200 x 380 x 210 mm Art.Nos.: SDS02.213 Extension Panel 13-line 62kg SDS02.214 Extension Panel 14-line 63kg SDS02.215 Extension Panel 15-line 64kg SDS02.216 Extension Panel 16-line 65kg SDS02.300 Repeater Panel for Wall Mounting SDS-R48/G Required for remote indication of fire and fault alarms. Dimensions of enclosure without fittings (H x B x D): 122 x 220 x 80 mm Weight: 1,8kg SMOKE DETECTION SYSTEM SDS TEST RESET DIAGNOSES ON- / OFFLINE ON FAULT ACCEPT FIRE safetec SWITCH FANS SDS02.301 Repeater Panel for Console Mounting SDS-R48/P Required for remote indication of fire and fault alarms. Dimensions of enclosure without fittings (H x B x D): 122 x 220 x 60 mm Weight: 1,8kg SMOKE DETECTION SYSTEM SDS DIAGNOSES ON- / OFFLINE ON FAULT ACCEPT FIRE TOGGLE FANS safetec TEST RESET Donnerstag, 1. November 2007 Page 3 Product Catalogue Smoke Detection System SDS-48 safetec Art.No. Description Type Remarks Outline SDS02.440 Fan Unit SDS0440 220/230V,50/60Hz Standard - type Prime mover = electric motor Fan wheel directly driven by shaft Dimensions (H x B x D): 337 x 886 x 428 mm Weight: 45kg Power Supply: 220/230VAC; 50/60Hz; 370W@50Hz, 440W@60Hz SDS02.441 Fan Unit SDS0441 110/115V, 60Hz Standard - type Prime mover = electric motor Fan wheel directly driven by shaft Dimensions (H x B x D): 337 x 886 x 428 mm Weight: 45kg Power Supply: 110/115VAC; 60Hz; 440W SDS02.445 Fan Unit SDS-M0440 with Housing 220/230V, 50/60Hz Fan Unit SDS02.440 in special GFK housing. Colour: White (RAL 9010) Weight: 63 Kg Dimensions: 123 x 64 x 38 SDS02.446 Fan Unit SDS-M0441 with Housing 110/120V, 60Hz Fan Unit SDS02.441 in special GFK housing. Colour: White (RAL 9010) Weight: 63 Kg Dimensions: 123 x 64 x 38 Donnerstag, 1. November 2007 Page 4 Product Catalogue Smoke Detection System SDS-48 safetec Art.No. Description Type Remarks Outline B30.001 Smoke Generator with integrated Fan Vulkan Produces smoke with special tobacco. The strength of the smoke generation can be controlled with the fan. Recommended for smoke tests with cargo hold smoke detection systems. Dimensions: 22 x 10 cm Weight: 734g 2. Accessories B30.004 Starter for Tobacco Helps to light the tobacco in the smoke generator Dimensions: 13 x 9,5 x 1 cm Weight: 40g B30.006 Tobakko for Smoke Generator, 500 g medium To be used in smoke generator B30.001. Weight: 500g BG01.930 Hose Fitting 3/4" male thread for PVC-hose 13/20mm Suitable for connection of flexible PVC-hose (Z02.002) to some types of 3-way valves, consisting of: - straight connector for PVC-hose (Z02.002) - sealing ring, fibre - reduction nipple 3/4" x 1/2", brass - sealing ring, copper Weight: 104g Donnerstag, 1. November 2007 Page 5 Product Catalogue Smoke Detection System SDS-48 safetec Art.No. Description Type Remarks Outline BG02.03x PVC-Hose Socket with Clamps The size of PVC-Hose Socket with Clamps and Reductions depends on total number of detection lines, see the drawing BG02.03x. Suitable for: 1. connection of air inlet- and outlet pipes (steel pipe size, see the drawing BG02.03x) to air fan units SDS01.420 / SDS01.430 / SDS01.440 2. connection of air outlet pipe (steel pipe size, see the drawing BG02.03x) to smoke detection panels / extension panel BG02.861 Prefilter for SDS-System SDS-2/6, SDS-48 Special Filters to prevent soiled Smoke Detectors. Suitable in front of 3-Way-Valves. Weight: 350g Outer diam.: 60 mm Length: 200 mm BG02.908 Fire Alarm Relay Module for max. 8 Lines System: SDS-48 The Fire Alarm Relay Module offers 8 voltage-free contacts for individual indication of fire alarm in each line. It can be placed into the smoke detection panel. DOK02.041 Manual for SDS-48, German Version SDS-48 Size: DIN A4 Weight: ca. 330g Rauchmeldesystem SDS-48 Für Schiffsladeräume nach SOLAS Chapter II-2 Regulation 13-1 Anwender - Handbuch DOK02.041 29.10.2000 Ausgabe 1.1 SMOKE DETECTION SYST EM SDS TEST RESET DIAGNOSES ON- / OFFLINE ON FAULT ACCEPT FIRE TOGGLE F ANS safetec DOK02.051 Manual for SDS48, English Version SDS-48 Size: DIN A4 Weight: ca. 330g Smoke Detection System SDS48 For Cargo Holds Onboard Ships acc. to SOLAS Chapter II-2 Regulation 13-1 Operating Manual DOK02.041 issue: preliminary 02.03.2000 SMOKE DETECTION SYSTEM SDS T EST RESET DIAGNOSES ON- / OFFLINE ON FAU LT ACCEPT FIRE TOGGLE FANS safet ec Donnerstag, 1. November 2007 Page 6 Product Catalogue Smoke Detection System SDS-48 safetec Art.No. Description Type Remarks Outline E02.005 External Sounder B/C 28 The external sounder may be mounted in a prepared blind boring in the smoke detection panel. If the sounder shall be mounted to a repeater panel, please order repeater panel together with the external sounder. Dimensions: 43 x 48 mm Weight: 40g Loudness: 85 dB/1m E08.803 Aerosol Test Gas 250 ml The test spray allows simulation of smoke to test a smoke detector. Content: 250 ml Weight: 250g G05.002 Door Arret SZ 2519 Suitable to arret front doors of smoke detection panels and extension panels in open position (1 pce per each door required) Weight (set): 218g Z01.002 Pipe Connector 3/4"female thread 1/2a x 3/4i Allows direct connection of DN20 steel pipe to the smoke detection panel and extension unit. Use it instead of the connection for flexible PVC - hose. Weight: 72g Z02.002 Flexible Hose (PVC), inner diam. 13 mm Guttasyn Material: PVC 8020 / 7020 Color: 29101 transparent nominal pressure at 20°C: 10 bar Suitable for connection between air sample inlets of smoke detection panels / extension panels / 3-way valves. Weight per m: 229g Donnerstag, 1. November 2007 Page 7 Product Catalogue Smoke Detection System SDS-48 safetec Art.No. Description Type Remarks Outline Z02.004 Flexible Hose with Spiral, inner diam.50 mm Airduc PVC 343, gray Suitable for connection between smoke detection panels and air fan units, when steel pipe laying causes problems (to be approved by class surveyor). Material: - PVC - steel spiral Colour: gray Weight per m: 541g Z02.006 Flexible Hose green, inner diam.: 50mm Heliflex Suitable for connection between smoke detection panels and air fan units, when steel pipe laying causes problems (to be approved by class surveyor). Material: - PVC - spiral Colour: green Weight per m: 500g Z02.014 Hose Clamp, 50-70 mm galvanized 50 - 70 mm diameter, suitable for connection of PVC-hoses Z02.006, Z02.070 or for other purposes. Material: steel, galvanized Weight: 40g Z02.017 Hose Clamp, 70-90 mm galvanized 70-90 mm diameter, suitable for connection of PVC-hose Z02.071 or for other purposes. Material: steel, galvanized Weight: 45g Z02.018 Hose Clamp, 90-110 mm galvanized 90-110 mm diameter, suitable for connection of PVC-hose Z02.072 or for other purposes. Material: steel, galvanized Weight: 50g Donnerstag, 1. November 2007 Page 8 Product Catalogue Smoke Detection System SDS-48 safetec Art.No. Description Type Remarks Outline Z02.070 Flexible Hose green, inner diam.: 63mm Heliflex Suitable for connection between smoke detection panels and air fan units, when steel pipe laying causes problems (to be approved by class surveyor). Material: - PVC - steel spiral Colour: green Weight per m: 500g Z02.071 Flexible Hose green, inner diam.: 75mm Heliflex Suitable for connection between smoke detection panels and air fan units, when steel pipe laying causes problems (to be approved by class surveyor). Material: - PVC - steel spiral Colour: green Weight per m: 541g Z02.072 Flexible Hose green, inner diam.: 90mm Heliflex Suitable for connection between smoke detection panels and air fan units, when steel pipe laying causes problems (to be approved by class surveyor). Material: - PVC - steel spiral Colour: green Weight per m: 541g Z03.008 Adapter Nipple 75/63 mm x 2 1/2"AG Air outlet connection of smoke detection panels and extension units (included in standart scope of supply). Weight: 150g Lenght: 88 mm Z04.003 PVC-Elbow 90° 50 mm inner diam. Suitable for DN40 pipe installation between smoke detection panels and fan-unit (alternativly to steel piping). Material: PVC Weight: 150g Donnerstag, 1. November 2007 Page 9 Product Catalogue Smoke Detection System SDS-48 safetec Art.No. Description Type Remarks Outline Z04.004 PVC-Elbow 90° 63 mm inner diam. Suitable for DN50 pipe installation between smoke detection panels and fan-unit (alternativly to steel piping). Material: PVC Weight: 170g Z04.005 PVC-Elbow 90° 75 mm inner diam. Suitable for DN65 pipe installation between smoke detection panels and fan-unit (alternativly to steel piping). Material: PVC Weight: 200g Z04.006 PVC-Elbow 90° 90 mm inner diam. Suitable for DN80 pipe installation between smoke detection panels and fan-unit (alternativly to steel piping). Material: PVC Weight: 250g Z04.010 PVC-Tee 50 mm inner diam. Suitable for DN40 pipe installation between smoke detection panels and fan-unit (alternativly to steel piping). Material: PVC Weight: 200g Z04.011 PVC-Tee 63 mm inner diam. Suitable for DN50 pipe installation between smoke detection panels and fan-unit (alternativly to steel piping). Material: PVC Weight: 220g Donnerstag, 1. November 2007 Page 10 Product Catalogue Smoke Detection System SDS-48 safetec Art.No. Description Type Remarks Outline Z04.012 PVC-Tee 75 mm inner diam. Suitable for DN65 pipe installation between smoke detection panels and fan-unit (alternativly to steel piping). Material: PVC Weight: 250g Z04.013 PVC-Tee 90 mm inner diam. Suitable for DN80 pipe installation between smoke detection panels and fan-unit (alternativly to steel piping). Material: PVC Weight: 300g Z04.015 PVC-Reduction short 63-50 mm Fitting suitable between SDS-48 and flexible hose Z04.016 PVC-Reduction, inner diameter 75 mm 75 mm to DN50 Fitting suitable between fan-unit and flexible hose Z04.020 PVC-Extension, GF, short 75 mm to 90 mm Fitting suitable between SDS-48 and flexible hose Donnerstag, 1. November 2007 Page 11 Product Catalogue Smoke Detection System SDS-48 safetec Art.No. Description Type Remarks Outline Z05.001 PVC-Pipe, outer diam. 90mm for DN80 pipes Suitable adaptor pipe fitting to connect DN80 steel pipes to smoke detection panels and extension units. Material: PVC Weight: 70g Length: 80mm Z05.002 PVC-Pipe DN80 - 90x4,3 mm 6m-length 6m-length Suitable for pipe installation between smoke detection panels and fan-unit (alternativly to steel piping). Material: PVC Weight per m: 1100g outer diam.: 90 mm Z05.003 PVC-Pipe DN40 - 50x3,7 mm 5m-length Suitable for pipe installation between smoke detection panels and fan-unit (alternativly to steel piping). Material: PVC Weight per m: 700g outer diam.: 50mm Z05.004 PVC-Pipe DN50 - 63x3,6 mm 6m-length Suitable for pipe installation between smoke detection panels and fan-unit (alternativly to steel piping). Material: PVC Weight per m: 800g outer diam.: 63mm Z05.005 PVC-Pipe, outer diam. 75mm for DN65 pipes Suitable adaptor pipe fitting to connect DN65 steel pipes to smoke detection panels and extension units. Material: PVC Weight: 70g Length: 80mm Donnerstag, 1. November 2007 Page 12 Product Catalogue Smoke Detection System SDS-48 safetec Art.No. Description Type Remarks Outline Z05.006 PVC-Pipe, outer diam. 50mm for DN40 pipes Suitable adaptor pipe fitting to connect DN40 steel pipes to smoke detection panels and extension units. Material: PVC Weight: 60g Length: 80mm Z05.007 PVC-Pipe, outer diam. 63mm for DN50 pipes Suitable adaptor pipe fitting to connect DN50 steel pipes to smoke detection panels and extension units. Material: PVC Weight: 70g Length: 80mm Z05.008 PVC-Pipe DN40 - 50x3,7 mm 1m-length Suitable for pipe installation between smoke detection panels and fan-unit (alternativly to steel piping). Material: PVC Weight per m: 700g outer diam.: 50mm Z05.009 PVC Socket inner diam. 50mm Suitable adaptor pipe fitting to connect DN40 steel pipes. Material: PVC Weight: 70g Length: 65mm Z05.012 PVC pipe socket inner diam. 63mm Suitable adaptor pipe fitting to connect DN50 steel pipes. Material: PVC Weight: 140g Length: 80mm Donnerstag, 1. November 2007 Page 13 Product Catalogue Smoke Detection System SDS-48 safetec Art.No. Description Type Remarks Outline Z05.013 PVC pipe socket inner diam. 75 mm Suitable adaptor pipe fitting to connect DN65 steel pipes. Material: PVC Weight: 250g Length: 92mm Z05.018 PVC pipe socket inner diam. 90 mm Suitable adaptor pipe fitting to connect DN80 steel pipes. Material: PVC Weight: 390g Length: 106mm Z05.025 PVC-Pipe DN65 - 75x3,6 mm 5m-length Suitable for pipe installation between smoke detection panels and fan-unit (alternativly to steel piping). Material: PVC Weight per m: 900g outer diam.: 75mm Z07.002 Vent Check Valve DN 50 Bolero Suitable for installation at end of air sampling line to atmosphere. O.D. x t = 60,3 x 6,3 DIN 2448 / 1629 ST 35 Weight: 5,8kg Z12.010 3-Way-Valve DN20 / PN160 Suitabel armature switch over from air suction to CO2 - discharge direction in case of fire. Weight: 1624g Donnerstag, 1. November 2007 Page 14 Product Catalogue Smoke Detection System SDS-48 safetec Art.No. Description Type Remarks Outline Z90.001 PVC-Elbow 90°, with sockets outer diam. 50mm Suitable adaptor pipe fitting to connect 1 1/2" steel pipes to smoke detection panels and extension units. Material: PVC Weight: 280g Z90.010 PVC-Tee, with hose sockets outer diam. 50mm Suitable adaptor pipe fitting to connect 1 1/2" steel pipes to smoke detection panels and extension units. Material: PVC Weight: 400g Z90.012 PVC-Reduction 75mm to DN40 Fitting consisting of Z04.016 and Z05.006 BG02.001 Spare Parts Set, stowed inside SDS Panel System SDS-48 Content: 10 pcs fuse 6,3 A t, time-lag, art.no. F03.035 10 pcs fuse 250 mA t, time-lag, art.no. F03.111 2 pcs sealing for motor shaft, art.no. FAN02.035 1 pc spare key for SDS-48 G04.100 3 pcs blind glands M20x1,5, art.no. W40.720 2 pcs blind glands M25x1,5, art.no. W40.725 Weight: 115g 3. Spare Parts Donnerstag, 1. November 2007 Page 15 Product Catalogue Smoke Detection System SDS-48 safetec Art.No. Description Type Remarks Outline BG02.301 Adapter Module for Repeater Panel System SDS-48 PCB in repeater panel with screwed terminals for cable connections and flatcable - connector for indication - / control module ... . The adapter - pcb contains relays and terminals for fire, fault and general alarm as well as terminals for external buzzer. Dimensions: 110 x 60 mm Weight: 70g BG02.500 Control Module for Smoke Detection Panel System SDS-48 The control module is mounted behind the front door of the smoke detection panel. It contains LC - display, LEDs and push - button for the operation of the system. Dimension: 182 x 105 x 38 Weight: 270g BG02.510 Control Module for Repeater Panel System SDS-48 The control module is mounted behind the front cover of the repeater panel. It contains LC - display, LEDs and push - button for the operation of the system. Dimension: 182 x 105 x 38 Weight: 270g BG02.600 Power Supply Module 220/230V System SDS-48 The power supply unit is mounted inside the smoke detection panel. It contains all power connections for main and emergency supply and for the fan unit as well as fuses and terminals for relay contacts. Dimensions: 187 x 167 x 55 mm Weight: 1,2kg BG02.610 Power Supply Module 110V/ 115V System SDS-48 The power supply unit is mounted inside the smoke detection panel. It contains all power connections for main and emergency supply and for the fan unit as well as fuses and terminals for relay contacts. Dimensions: 187 x 167 x 55 mm Weight: 1,2kg Only for 110V/ 115V supply! Donnerstag, 1. November 2007 Page 16 Product Catalogue Smoke Detection System SDS-48 safetec Art.No. Description Type Remarks Outline BG02.810 Detector Connection Module, 4 Lines + Extension System SDS-48 PCB to connect up to 4 smoke detectors and airflow indicators. Dimensions: 244 x 46 mm Weight: 72g BG02.820 Detector Connection Module, 8 Lines + Extention System SDS-48 PCB to connect up to 8 smoke detectors and airflow indicators. Dimensions: 488 x 46 mm Weight: 136g E01.003 Airflow Indicator (Pressure Switch) Type 605 The airflow indicator (pressure switch 0,3 mbar) is mounted in the upper enclosures of the smoke detection panels and extension units. Dimensions: D=81 mm H=74 mm Weight: 120g Remark: If the predecessor E01.001 shall be replaced, please order plug and cable BG02.090, too. E06.101 Galvanic Isolator EEx, 1 Channel, for SDS-48 KFD0-CS-Ex1.54 The galvanic isolator serves as a safety barrier for intrinsically safe operation of the smoke detectors and airflow indicators. This type contains 1 channel. Dimensions: 112 x 93 x 20 mm Weight: ca. 100g E06.102 Galvanic Isolator EEx, 2 Channels, for SDS-48 KFD0-CS-Ex2.54 The galvanic isolator serves as a safety barrier for intrinsically safe operation of the smoke detectors and airflow indicators. This type contains 2 channels. Dimensions: 112 x 93 x 20 mm Weight: ca. 100g Donnerstag, 1. November 2007 Page 17 Product Catalogue Smoke Detection System SDS-48 safetec Art.No. Description Type Remarks Outline E20.002 Optical Smoke Detector XP95 I.S. System SDS-48 The smoke detectors are located in the detector boxes of the smoke detection panel and the extension panel. Dimensions: 100 x 50 mm (including socket) Weight: 161g (including socket) E20.004 Socket for Smoke Detector System SDS-48 The sockets for smoke detectors are located in the detector boxes of the smoke detection panel and the extension panel. Dimensions: 100 x 50 (including smoke detector) Weight: 161g (including smoke detector) FAN02.017 Impeller, Steel, for SDS02.440/441 Suitable for installation on FAN-unit SDS02.440 and SDS02.441. Dimensions: Diam. 300mm Weight : 2,2 Kg FAN02.035 Sealing for motor shaft, for SDS02.440 PTFE Suitable for installation on FAN-unit SDS02.440 and SDS02.441 Weight: 8g FAN02.036 Ball bearing for Fan Unit SDS-M0430 / M0440 Type 6202 2Z C3 For fan unit SDS-M0430 with motor type "Hanning" Location: opposite of shaft side Dimensions: D = 35, H = 10 mm Weight: 50g Donnerstag, 1. November 2007 Page 18 Product Catalogue Smoke Detection System SDS-48 safetec Art.No. Description Type Remarks Outline FAN02.037 Ball bearing for Fan Unit SDS-M0430 / M0440 Type 6204 2Z C3 for fan unit SDS-M0430 with motor type "Hanning". Location: shaft side Dimensions: D = 35, H = 10 mm Weight: 50g FAN02.114 Capacitor for Fan Unit SDS-M0441, Motor: Hanning 40 µF 240VAC Suitable for installation on electric motor FAN02.131. length: 130 mm Diam.: 45 mm FAN02.116 Capacitor for Fan Unit SDS-M0440 10 µF450VAC, P2, Alu Suitable for installation on electric motor FAN02.121. Length: 100 mm Diam.: 35mm Weight: 50g FAN02.121 E-Motor,1Ph. 230V, 50/60Hz, Hanning, for Fan Unit E7KC2B5-7-378 Suitable for installation on SDS 02.440. Diam.: 350 mm Weight: 6,1 Kg FAN02.131 E-Motor,1 Ph. 110V,60Hz E7KC2B5-7-387 Suitable for installation on SDS02.441. Diam.: 350 mm Weight: 6,1 Kg

Write Your Own Review
You're reviewing:Safetec BG02.600 BG02.610 Power Supply Module System SDS-48
Safetec BG02.600 BG02.610 Power Supply Module System SDS-48